Index > Product > Copolymer Coated > Copolymer Coated Aluminum Tape
Copolymer coated copper tape applies for medium and high voltage power cables as a shield/moisture barrier as a moisture/ chemical barrier for cable core, it consists of a copper tape coated on single side with a special ethylene copolymer color-coded green. The coating forms a strong moisture-resistant bond to the copper substrate that will not delaminate from contact with the copper. The coatings also form strong polymeric bonds to zero halogen, polyethylene and chlorinated polyethylene jacketing resins during the jacket extrusion process thereby allowing fabrication of “bonded jacket” or laminate sheath, cables. The copper alloy is fully annealed which has high conductivity and easy fabrication characteristics.
Property | Unit | Values | Test Method | |
Thickness | Cu | 0.15/0.20 | mm | |
EAA | 0.05 | mm | ||
Tensile Strength | MPa | ≥180 | ASTM B152 | |
Elongation | % | ≥20 | ASTM B152 | |
Peel strength | N/cm | ≥5 | ASTM B736 | |
Heat Seal strength | N/cm | ≥17.5 | ASTM B736 | |
Corrosion resistance | Grade | 7 | ||
Filler/ Flood Resistance 68 deg C/168 hrs | No Delamination | ASTM B736 | ||
Water Resistance 68 deg Cl 168 hrs, Peel Strength68℃ | N/cm | ≥5 | ASTM B736 | |
Dielectric Strength Two-Side, DC 1 Kv | No Break | |||
conductivity | IACS | ≥90% |
Inner Diameter |
Width |
Length |
Roll core material |
76/150/406mm |
10mm-1000mm |
2000m without joints | paper/steel/plastic cire |
Keep the warehouse clean. Avoid exposure to direct sunlight, pollution and all damage cuased by external forces.
Skilled operators should take or lay the materials gently, avoid scrap and crash problems.
The above mentioned data sheet should, however, only be regarded as a general guide to product properties and not as a guarantee. Some of the properties can be changed as a result of our efforts to improve the quality of our products. All listed test method is just for reference, actual test performed according to modified equipment and conditions.